System 5000 Systems: ACM-16AT and ACM-32A Only
PN 15842:K 7/23/2002 81
2. These control switches are active only if all of the following conditions are
set:
• Receive Only (DIP Switch #5) is set to “OFF”.
• Switch Inhibit (DIP Switch #7) is set to “OFF”.
3. These status LEDs are active only when the system is programmed for
“Output Status”.
4. These control switches require that the system be programmed for “Output
Control”.
5. The ACS annunciates the eight AIM-200 software zones only, except as
described below.
6. With Software P/N#S5000R7.0 or higher installed in the System 5000, the
manner in which IZM-8 circuits programmed as supervisory are
annunciated depends upon whether Mode 1 or Mode 2 is selected.
7. Annunciator Point #7 yellow LED indicates Municipal Tie Trouble if no
UDACT is installed. It will annunciate Low Battery/Ground Fault if a
UDACT is installed in the system.
S.7 AIM-200 Point Annunciation
The ACS can annunciate
up to 192 intelligent
devices mapped by an
AIM-200. The AIM-200
must be installed
directly to the right of
the control panel.
This option provides
annunciation of up to
256 points for the
System 5000; one
possible configuration is
shown in the
accompanying
illustration.
Note that an annunciator
controls standard
System zones; it cannot
be used to execute
manual ON/OFF control
of intelligent AIM-200
points.
Annunciator
Address 1:
• 8 control panel points (control panel point shift not an option).
• 8 unusable points (redundant AIM-200 points).
J1 1J1 1
8 control
panel points
48 points mapped to modules in
positions 3, 4, 5, 6, 7 and 8
8 unusable
AIM-200 points
aim200point.cdr