System 5000 Systems: ACM-16AT and ACM-32A Only
82 PN 15842:K 7/23/2002
48 points mapped to the next six modules installed in the System (which
can also be AIM-200s for annunciation of their eight software zones).
Annunciator Address 2:
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to
the control panel.
Annunciator Address 3:
Addressable Modules, addressed 1-64, on the AIM-200 installed next to
the control panel.
Annunciator Address 4:
Intelligent Detectors, addressed 65-96, followed by Addressable
Modules, addressed 65-96, on the AIM-200 installed next to the control
panel. The control panel’s programming manual provides programming
instructions for this option. Refer to program choice “AIM(256)”.
Note: AIM-200 detector and module addresses 97, 98, and 99 may be used, but
cannot be point-annunciated.