System 5000 Systems: ACM-16AT and ACM-32A Only
76 PN 15842:K 7/23/2002
APPENDIX S System 5000 Systems: ACM-16AT
and ACM-32A Only
S.1 Capabilities
When installed with a System 5000, the ACS can annunciate the status of
initiating and notification circuits, relays, and several system control functions.
Each annunciator LED is automatically assigned to one and only one system
point.
Circuits:
IZM-8 Initiating Device Circuits (alarm and trouble)
ICM-4/ICE-4 Notification Appliance Circuits (trouble)*
CRM-4/CRE-4 Control Relays (trouble)*
TCM-2 circuits (trouble)*
TCM-4 circuits (trouble)*
VCM-4/DCM-4 circuits (trouble)*
AIM-200 zones (alarm and trouble)
*Indication of output circuit activation can be obtained by programming the
control panel for “OUTPUT STATUS.”
System Controls:
Acknowledge
Signal Silence
System Reset
Activate Notification Circuits 1 and 2, the Remote Signalling Municipal Tie
circuit, and the Alarm Relay.
S.2 Connecting the EIA-485 Circuit
Communication between the
control panel and the Annunciator
Control System is accomplished
over a two-wire EIA-485 serial
interface. This communication
circuit is supervised by the System.
To operate the ACS, the control
panel must be Revision D or
greater. The revision level of the
control panel is marked on a label
affixed to the upper board.
Additionally, the system must be
operating under control panel
software with U4 ROM part
number 73085 or higher.
Loss of communication results in
“System Trouble” and “Module Failure” indications at the control panel.
-
+
5000tb1.cdr
TB2 on main board
of System 5000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ACM-16AT and is the answer not in the manual?

Notifier ACM-16AT Specifications

General IconGeneral
BrandNotifier
ModelACM-16AT
CategoryFire Alarms
LanguageEnglish

Related product manuals