2. Use of the Controls Control Keys
18 NFS-640 Operations Manual P/N 51334:B 10/03/2003
System Reset
Use the SYSTEM RESET key to reset the control panel. When pressed, the control panel does the
following:
• Clears ALL active inputs
• Interrupts resettable power
• Sends a “System Reset” message to the History buffer, and installed printers, CRT-2 terminals,
and terminal mode LCD-80s
• Decouples from Noti•Fire•Net, if connected, for 60 seconds to allow Cooperative Control By
Event (CCBE) to clear.
If any alarm or trouble exists after you press the
SYSTEM RESET key, all NACs, control outputs, and
panel audio and visual indicators will reactivate.
Note: Trouble conditions will not clear and re-report upon RESET.
Note: If Local Control is set to “NO”, the FACP will not respond to SYSTEM
RESET.
Lamp Test
Use the LAMP TEST key to test the control panel LEDs, all installed panel circuits, and the panel sounder.
When pressed and held, the control panel does the following:
• Lights all control panel LEDs
• Turns on the panel sounder
• Lights all segments of the LCD display. When the
LAMP TEST key is held for longer than five
seconds, the LCD will display the Software Revisions.
• Lights all panel circuit LEDs