3. Operation of the Control Panel Disabled Points Mode of Operation
32 NFS-640 Operations Manual P/N 51334:B 10/03/2003
Disabled Points Mode of Operation
The control panel indicates disabled points by displaying a screen for each disabled detector, monitor
module, control/relay module, and Panel Circuit. Disabled points do not cause an alarm or any
Control-by-Event activity. If more than one point is disabled, the control panel automatically displays
each point in the sequence in which the point was disabled.
When one or more points are disabled, the control panel does the following:
Holds all disabled output points in the off-state
Flashes the
SYSTEM TROUBLE LED
•Lights the
POINT DISABLED LED
•Lights the
TROUBLE LED for each Panel Circuit with a disabled point
Sends a Disabled Point message to the LCD display, History buffer and installed printers,
terminal mode LCD-80s, and CRT-2s
Displays a message for each disabled point
Figure 14 Sample Disabled Point Message
!
CAUTION: Disabling a zone disables all input and output devices associated with the zone.
Disable message
Type Code of the disabled device
Address of the
disabled device
DISABL TAMPER INTENSIVE CARE UNIT
EASTERN WING 03:20P 071401 1M159
Custom descriptor for
this device location
Time and date of trouble
Extended 12 character
custom label
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals