EasyManuals Logo
Home>Notifier>Fire Alarms>NFS-640

Notifier NFS-640 User Manual

Notifier NFS-640
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
3. Operation of the Control Panel Output Circuit Trouble Mode of Operation
36 NFS-640 Operations Manual P/N 51334:B 10/03/2003
How the Control Panel Indicates a NAC Trouble
A Trouble occurring on a NAC causes the control panel to do the following:
Produce a pulsed audible tone
Flash the
SYSTEM TROUBLE LED
Turn on the Trouble relay (TB9)
Send a message to the LCD display, History buffer and installed printers, terminal mode LCD-
80s, and CRT-2s
Display a
TROUBL status banner and a CONTROL Type Code on the LCD display, along with
information specific to the device
Figure 17 Sample of a NAC in Trouble Message
How the Control Panel Indicates a Panel Circuit Trouble
A trouble occurring on a Panel Circuit causes the control panel to do the following:
Produce a pulsed audible tone
Flash the
SYSTEM TROUBLE LED
Turn on the Trouble relay (TB9)
Send a message to the LCD display, History buffer and installed printers, terminal mode LCD-
80s, and CRT-2s
Display a
TROUBL status banner and CONTROL Type Code on the LCD display, along with
information specific to the device
Figure 18 Sample of a Panel Circuit in Trouble Message
How the Control Panel Indicates a Control/Relay Trouble
A trouble occurring on a control/relay module or control/relay transponder causes the control panel to
do the following:
Produce a pulsed audible tone
Flash the
SYSTEM TROUBLE LED
Turn on the Trouble relay (TB9)
Send a message to the LCD display, History buffer and installed printers, terminal mode LCD-
80s, and CRT-2s
Display a
TROUBL status banner and CONTROL Type Code on the LCD display, along with
information specific to the device
Figure 19 Sample of a Control/Relay Module in Trouble Message
Status banner
Type Code
Time and date of trouble
TROUBL CONTROL PANEL CIRCUIT NO. 2
OPEN 09:38A 071401 B02
Device Address
Type of Trouble
Custom Description for
this device location
TROUBL CONTROL PANEL CIRCUIT P8-8
OPEN 09:38A 071401 P8.8
Status banner
Type Code
Time and date of trouble
Device Address
Type of Trouble
Custom Description for
this device location
TROUBL CONTROL MODULE ADDR 1M044
OPEN 09:38A 071401 1M044
Status banner
Type Code
Time and date of trouble
Device Address
Type of Trouble
Custom Description for
this device location
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals