EasyManuals Logo
Home>Notifier>Fire Alarms>NFS-640

Notifier NFS-640 User Manual

Notifier NFS-640
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Viewing and Printing a Read Status 4. Read Status Operation
NFS-640 Operations Manual P/N 51334:B 10/03/2003 49
How to Read Status for Annunciator Selections
Annunciator Selection screens specify the information that displays on
ACS annunciators. From the “Read Status” screen, press 0, then press the
ENTER key. You can now view Read Status for System Functions as
follows: press Z, enter S, enter annunciation selection number (1-4), press
the
ENTER key. Sample LCD displays for the Read Status of Annunciator
Selection are shown below:
Figure 27 Annunciator Selection 1 Screen
To view the next three annunciator selection screens, press the (
NEXT SELECTION) key.
Figure 28 Annunciator Selection 2 Screen
If UDACT=N, the control panel displays the Annunciator Selections 3 and 4 screen, addresses A20-
A32, as shown below:
Figure 29 Annunciator Selections 3 and 4 Screens
An Annunciator Selection screen shows the information that will display on the ACS annunciators. The
table below contains the ACS display selections.
Table 12 ACS Selection Groups
1 through 9 Programmable Annunciator #1 through #9
0 Programmable Annunciator #10
A 8 Systems points + Zones 1-56
B Zones 57-99, 9 F zones, 8 R zones, 4NAC
C Loop 1, Modules 1-64
D Loop 2, Modules 1-64
E Loop 1, Modules 65-128
F Loop 2, Modules 65-128
G Loop 1, Modules 129-159 & Loop 2, Modules 129-159
H Loop 1, Detectors 1-64
I Loop 2, Detectors 1-64
J Loop 1, Detectors 65-128
K Loop 2, Detectors 65-128
L Loop 1, Detectors 129-159 & Loop 2, Detectors 129-159
M Panel circuits 1-1 to 8-8 (64)
N 8 Systems points + Zones 1-56, used for remote station communicator (TM-4)
O 8 Systems points + Zones 1-56, used for municipal box trip output (TM-4)
Annunciator addresses 1 to 19 can be programmed to any one of the above selections. If there is a
UDACT, selections A-M will be sent to Annunciator addresses 20 to 32 respectively.
A1=Address
ACS selection group
ANNUN SELECTION1: A1=H A2=* A3=* A4=*
A5=* A6=* A7=* A8=* A9=* A10=* A11=*
ANNUN SELECTION2: A12=* A13=* A14=*
A15=* A16=* A17=* A18=* UDACT=N
ANNUN SELECTION3: A20=* A21=* A22=*
A23=* A24=* A25=* A26=* A27=* A28=*
ANNUN SELECTION4: A29=* A30=* A31=*
A32=*
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals