3. Operation of the Control Panel Security Alarm Mode of Operation
28 NFS-640 Operations Manual P/N 51334:B 10/03/2003
Interpreting Security Type Codes
The Type Code that displays in the security alarm message indicates the type of security alarm being
generated by the monitor module that initiates the alarm. For example, a monitor module with a Type
Code of
AREA MONITOR indicates an intruder in a protected premises area. The table below lists the
Type Codes that can appear in a security alarm message.
Table 5 Security Type Codes
Monitor Modules
Type Code
Latching
(Y/N)
Purpose What it does
AREA MONITOR Y Monitors area surveillance equipment, such
as motion detectors
Lights SECURITY LED, activates CBE
SECURITY Y Monitors security switches for tampering Lights SECURITY LED, activates CBE
SYS MONITOR Y Monitors critical equipment for security Lights SECURITY LED, activates CBE