3. Operation of the Control Panel System Trouble Mode of Operation
26 NFS-640 Operations Manual P/N 51334:B 10/03/2003
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the following:
Returns to Normal operation (indicated by the “System Normal” message)
Sends an “System Normal” message to the LCD display, History buffer and installed printers,
terminal mode LCD-80s, and CRT-2s
Restores troubles automatically - even if troubles are not acknowledged
If multiple trouble conditions exist in the system, the LCD and optional terminal mode CRT-2 and
LCD-80s displays automatically step through each trouble every 3 seconds in the following order:
1. Alarms, in order of address
2. Supervisory, in order of address
3. Troubles, in order of address
Press the
ACKNOWLEDGE/SCROLL DISPLAY key and the display stops on the current trouble event for 1
minute, then begins to automatically step through remaining troubles. To manually step through
remaining troubles, press the
ACKNOWLEDGE/SCROLL DISPLAY key.
Refer to Appendix D: Point and System Troubles Lists on page 79 for explanations of troubles that
appear on the display.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
BrandNotifier
ModelNFS-640
CategoryFire Alarms
LanguageEnglish

Related product manuals