EasyManua.ls Logo

Notifier SFP-400B - Dip Switch Location and Descriptions

Notifier SFP-400B
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SFP-400B 15124:G1 06/24/97
24
1 2 3 4 5 6
O
N
To set a switch to the "ON" position,
slide it up.
Micro Fail LED
Battery Fail
LED
Ground Fault LED
3.7 Dip Switch Location and Descriptions
Switch 4: Silence Inhibit
If selected and an alarm occurs, the
ALARM SILENCE switch will not func-
tion until 60 seconds have passed since
initiation of the alarm. If another alarm
occurs, the timer will restart at 60 sec-
onds.
Switch 5: Disable Bells
When this switch is set "ON", the four
Indicating Appliance Circuits and the
SYSTEM ALARM relay will be disabled,
and a local trouble signal will be gener-
ated.
Switch 6: One Man Walk Test
Setting this switch to the "ON" position
places the control panel in Walk Test
Mode. The first alarm on Initiating Cir-
cuit under test will ring associated Indi-
cating Circuit(s) for 5 seconds. Zone
Alarm LED will flash. The second alarm
on Initiating Circuit under test will ring
associated Notification Circuit(s) for 1
second. Zone Alarm LED will illuminate
Steadily. A Trouble condition on Initiat-
ing Circuit under test will sound piezo
and light Zone Trouble LED.
Switch 1: Alarm Verification
If selected, alarm signals that occur on any zone will
be subjected to a two-minute verification period to
determine if the alarm is true. Note that the control
panel will distinguish if the alarm signal came from
a shorting-type contact device (manual pull station,
4 wire detector, or heat detector) or a two-wire
smoke detector, and will not employ verification of
alarm signals from the contact devices.
Switch 3: Supervisory on Zone 4
If set for Supervisory, Initiating Device Circuit 4 will
function as a supervisory circuit. Activation of a
tamper or other supervisory switch on this circuit will
not result in an alarm condition. The piezo will sound
a distinct pulsing tone and the yellow LED on zone
4 will flash along with the supervisory LED. Notifi-
cation Appliance Circuits 1 and 2 will activate (see
Section
"Output Circuits"
).
Switch 2: Waterflow on Zone 3
If set for Waterflow, Initiating Device circuit 3 will
function as a waterflow circuit. If an alarm occurs on
this zone, the ALARM SILENCE switch will not
silence any activated output circuits.
Note: The Reset key must depressed after any switch configuration has been made.

Related product manuals