G9SA
Specifications
Ratings
Power Input
Note: When an Expansion Unit is connected, the power consumption is increased by 2 VA/2 W max.
Inputs
Note: When an Expansion Unit is connected, the input current is increased by 30 mA max.
Contacts
Characteristics
Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
2. Not Including bounce time.
3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.
4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
5. The durability is for an ambient temperature of 15 to 35qC and an ambient humidity of 25% to 75%.
6. Weight shown is for 24-VAC/VDC type. For 100 to 240-VAC type, add approximately 20 g.
Item G9SA-301/TH301 G9SA-501 G9SA-321-T@
Power supply voltage 24 VAC/VDC:24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC:100 to 240 VAC, 50/60 Hz
Operating voltage range 85% to 110% of rated power supply voltage
Power consumption
(See note.)
24 VAC/VDC: 1.8 VA/1.7 W max.
100 to 240 VAC: 9 VA max.
24 VAC/VDC: 2.8 VA/2.6 W max.
100 to 240 VAC: 11 VA max.
24 VAC/VDC: 3.5 VA/3.3 W max.
100 to 240 VAC: 12.5 VA max.
Item G9SA-301/321-T@/TH301 G9SA-501
Input current (See note.) 40 mA max. 60 mA max.
Item G9SA-301/501/321-T@/TH301/EX301/EX031-T@
Resistive load
Rated load 250 VAC, 5 A
30 VDC, 5 A
Rated carry current 5 A
Item G9SA-301/TH301 G9SA-501/321-T@ G9SA-EX301/EX031-T@
Contact resistance (See note 1.) 100 m:
Operating time (See note 2.) 30 ms max.
Response time (See note 3.) 10 ms max.
Insulation resistance (See note 4.) 100 M: min. (at 500 VDC)
Dielectric
strength
Between different outputs 2,500 VAC, 50/60 Hz for 1 min
Between inputs and outputs
Between power inputs and outputs
Between power inputs and other inputs
(only for 100 to 240-V models)
Vibration resistance 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction
300 m/s
2
Malfunction
100 m/s
2
Durability
(See note 5.)
Mechanical 5,000,000 operations min. (at approx. 7,200 operations/hr)
Electrical 100,000 operations min. (at approx. 1,800 operations/hr)
Failure rate (P Level) (reference value) 5 VDC, 1 mA
Ambient operating temperature 25 to 55qC (with no icing or condensation)
Ambient operating humidity 35% to 85%
Terminal tightening torque 0.98 N·m
Weight (See note 6.) Approx. 210 g Approx. 270 g Approx. 130 g
http://www.ia.omron.com/
3
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron G9SA Series and is the answer not in the manual?

Omron G9SA Series Specifications

General IconGeneral
BrandOmron
ModelG9SA Series
CategoryRelays
LanguageEnglish

Related product manuals