4 - 121
4 Safety Function Blocks
NX-series Safety Control Unit Instructions Reference Manual (Z931)
4
SF_TestableSafetySensor
8003 32771 Wait for Reset 1 The FB is waiting for Reset to change to TRUE
after state 8002.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8004 32772 External Function Test The automatic sensor test failed. An external
manual sensor test is required. The FB started
support for the required external manual sensor
test (NoExternalTest = FALSE). The sensor sig-
nal must be made FALSE.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8005 32773 ESPE Interrupted
External Test
The automatic sensor test failed. An external
manual sensor test is required. The FB started
support for the required external manual sensor
test (NoExternalTest = FALSE). The sensor sig-
nal must be TRUE.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8006 32774 End External Test The automatic sensor test failed. An external
manual sensor test is required. The FB started
support for the required external manual sensor
test (NoExternalTest = FALSE). The external
manual test was completed. The FB detected the
completion of the sensor switching cycle (exter-
nal control).
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
DiagCode (hexadecimal)
DiagCode
(decimal)
Status name Status description and output results