7 Handling Errors
7 - 4
NA-series Programmable Terminal Soft-NA User’s Manual (V126)
Change the Ethernet interface card specification
at the Sysmac Studio or connect the Ethernet
cable to the specified Ethernet interface card.
Refer to the appendices of the Sysmac Studio
Version 1 Operation Manual (Cat. No. W504-E1) for
the procedure to specify the Ethernet interface card.
Yes
Yes
No
No
Is the same IP address
set for more than one node (e.g.,
Sysmac Studio or Soft-NA) in the
same domain?
Is the designated port
number used only by Sysmac
Studio and Soft-NA?
Can the Sysmac Studio go
online with the
PC
?
A
B
Replace the Ethernet cable or
Ethernet switch.
END
Set the IP addresses for Sysmac Studio and Soft-NA.
Yes
Yes
No
Yes
No
No
Is the same port number set on
Sysmac Studio and Soft-NA?
Yes
No
Can the Sysmac Studio go
online with the
PC
?
Can the Sysmac Studio go
online with the
PC
?
Check if any other application is using the
designated port number. If it is already in use,
select a different port number. In addition, check
if the designated port number is disabled by
firewall or others.
Make the Port setting same on both Communi-
cations Setup of Sysmac Studio and Device
System Menu - Interface Settings of Soft-NA.
Is the Ethernet cable
connected to the Ethernet interface card
that is specified to use for connection
in the Sysmac Studio?
Yes
Yes
No
No
Can the Sysmac Studio go
online with the
PC
?