7-2
TESTING GENERATOR
Winding Insulation Resistance Test
Procedure
A 500 VAC megger is recommended for the winding
insulation resistance tests prescribed below. A test
consists of applying the test potential between the
winding and ground (winding laminations) for a peri-
od of 10 minutes and recording resistance at 1 min-
ute and again at 10 minutes.
Resistance values of at least 5 megohms should be
obtained for a new generator with dry windings. The
polarization index should also be at least 2 (the ratio
of the resistance reading at ten minutes to the read-
ing at one minute). For a set that has been in ser-
vice, the resistance reading should not be less than
1 megohm nor the polarization index less than 2.
Dry the windings if low readings are obtained or the
set has been in standby for a long time in high hu-
midity conditions and repeat the test.
Winding Resistance Test Procedure
Use a digital ohmmeter or Wheatstone bridge to
measure winding resistance. The device should
have a precision of at least 0.01 ohm.
Break-Out Tool 300-5512
Break-out tool 300-5512 for use in conjunction with
an accurate digital multi-meter is available for pre-
forming stator winding output tests while running the
genset. The tool is plugged into the genset wiring
harness in place of the genset control. Follow the
tool instructions.