168
20. Service Data
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
20.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
- Indoor room temperature: 27°C DryBulb/19°C Wet Bulb
- Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
- Compressor frequency: Rated for cooling operation
- Piping length: 5m
- Voltage: 230/240V
20.1.1 CS-Z20TKR CU-Z20TKR
1.200
1.400
1.600
1.800
2.000
2.200
2.400
2.600
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Current (A)
Outdoor Temperature (℃)
230V 240V
0.800
0.900
1.000
1.100
1.200
1.300
1.400
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Lo Pressure (MPa)
115.000
130.000
145.000
160.000
175.000
190.000
205.000
Lo Pressure (Psi)
Outdoor Temperature (℃)
230V 240V
15.000
16.000
17.000
18.000
19.000
20.000
21.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Indoor
scharge
Air Temperature (℃)
Outdoor Temperature (℃)
230V 240V
230V 240V
16 1.290 1.240
25 1.580 1.530
35 2.000 1.950
46 2.460 2.410
16 0.861 124.878
25 1.006 145.908
35 1.160 168.244
46 1.346 195.221
16
25
35
46
Outdoor
Temperature (°C)
Current (A)
15.470
16.870
20.630
Outdoor
Temperature (°C)
Outdoor
Temperature (°C)
Indoor Discharge
Air Temperature (°C)
15.950
Lo Pressure
(MPa)
Lo Pressure
(Psi)