6. SPECIFICATIONS
TYPE
INSPIRE 906-ES
INSPIRE 910-ES
CAPACITY*
6000 VA / 5400 W
10000 VA / 9000 W
INPUT
Voltage
Range
Low Line Loss
110 VAC ± 3% at 50% Load;
176 VAC ± 3% at 100% Load
Low Line Comeback
Low Line Loss Voltage + 10V
High Line Loss
300 VAC ± 3 %
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Power Factor
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100% ~ 110%: 30min; 110% ~ 130%: 5min; > 130%: 10sec
Battery mode
100% ~ 110%: 3min; 110% ~ 130%: 30sec; > 130%: 10sec
Current Crest Ratio
3:1 max
Harmonic Distortion
3 % THD (Linear Load)
5 % THD (Non-linear Load)
Transfer
Time
Line Battery
0 ms
Bypass Inverter
0 ms
EFFICIENCY
AC mode
> 92%
> 93%
Battery Mode
> 90%
> 91%
BATTERY
Standard
Model
Battery Type
12 V / 9 Ah
Numbers
16
16
Recharge Time
9 hours recover to 90% capacity
Charging Current
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
Charging Voltage
218.4V ± 1%
218.4V ± 1%
PHYSICAL
Standard
Model
Dimension D*W*H(mm)
369 x 190 x 688
442x 190 x 688
Net Weight (kgs)
61
66
ENVIRONMENT
Operation Temperature
0 ~ 40°C
(battery life cycle will be shorten when temperature is above 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB @ 1 Meter
Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix,
and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Lower capacity to 60% of capacity in CVCF mode and up to 90% when output voltage is adjusted to 208VAC.
** If the UPS is installed or used in places with altitudes above 1000m, the output power should be lowered by one percent per 100m.
Product specifications are subject to change without further notice.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PROLiNK Professional II+ Series and is the answer not in the manual?

PROLiNK Professional II+ Series Specifications

General IconGeneral
BrandPROLiNK
ModelProfessional II+ Series
CategoryUPS
LanguageEnglish

Related product manuals