6. SPECIFICATIONS
110 VAC ± 3% at 50% Load;
176 VAC ± 3% at 100% Load
Low Line Loss Voltage + 10V
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100% ~ 110%: 30min; 110% ~ 130%: 5min; > 130%: 10sec
100% ~ 110%: 3min; 110% ~ 130%: 30sec; > 130%: 10sec
≦ 3 % THD (Linear Load)
≦ 5 % THD (Non-linear Load)
9 hours recover to 90% capacity
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
0 ~ 40°C
(battery life cycle will be shorten when temperature is above 25°C)
Supports Windows 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix,
and MAC
Power management from SNMP manager and web browser
* Lower capacity to 60% of capacity in CVCF mode and up to 90% when output voltage is adjusted to 208VAC.
** If the UPS is installed or used in places with altitudes above 1000m, the output power should be lowered by one percent per 100m.
Product specifications are subject to change without further notice.