6
15
QUICK REFERENCE GUIDES
LIMITED USER FUNCTIONS
1. Unsetting. Enter (Limited User Code)
2. Full set. Enter (Low Tone Volume)
or (Max Tone Volume)
3. Part set. Enter or (Low Tone Volume)
Enter or (Low Tone Volume)
Enter (Low Tone Volume)
4. Clear flashing Alarm LED. Enter (Limited User Code)
5. Zone omit on exit. Enter
6. Instant Fire Alarm. Enter
7. Instant Panic Alarm. Enter
8. Chime on/off. Enter
9. Read Log. Enter. To scroll forward: . To scroll back: .
Symbols stored in the log and their meaning:
Entry/Exit zone activation.The panel was not unset before
the end of the entry time period, or User did not leave in time.
to Activation of a programmable zone.
This shows that a zone was omitted and refers to the
number which precedes it in the log.
Tamper fault or sabotage.
Personal attack activation.
Fire alarm activation.
Leaving read-log function. Enter
The panel will not set if the Entry / Exit tone is not heard.
In this case, re-enter the building via the Entry / Exit route and enter your Limited or
Master user code.
Read the event log and then clear or omit the relevant zone. (See 'Omitting One or More
Zones', Page 9)
After setting, if any of the immediate zones are not clear, the alarm light will begin to
flash and a fault state will be indicated by a loud repeated low tone.
Clear the relevant zone or omit it on exit as above. (See 'Omitting One or More Zones',
Page 9)
5 ZONES
Engineer Programmable Zones
Entry / Exit This is a zone which allows limited-time access to the
premises in order to set or unset the system.
Access This is a zone which, on setting the panel, allows access
to the Entry / Exit Zone. However, if the panel is set and
an Access zone is triggered before an Entry / Exit zone
then an alarm will be generated immediately.
Immediate This is a zone which will, when entered, go into alarm
when the panel is set.
Omitted If a zone is programmed as an Omitted zone by the
Engineer, then it is ignored by the panel. Primarily used
for Part set options. It also allows the user to continue to
use the alarm system even if a fault has been discovered
on one or more zones.
24 hour zones
Personal Attack
Zone Triggering of the Personal Attack zone will always cause a
full alarm activation regardless of whether or not
the panel is set.
Tamper A tamper zone activation will only generate an internal
alarm, if the panel is in Day mode. If a tamper fault is
present and the panel is then set, the system will give a
second internal alarm. Triggering of a tamper zone when
the panel is set will always give an external as well as
internal alarm.
Fire Triggering of the fire zone will only operate the internal
sounder. A fire alarm is identified by a three note rising
sound which is easily distinguished from all other tones.
Zone
number(s)
RDOC147Kissue3