6.3 208/240V AIRFLOW PERFORMANCE DATA – RHBL (CONSTANT TORQUE MOTOR)
Nominal
Cooling
Capacity
Tons
Manufacturer
Recommended
Air-Flow Range
(Max/Min) CFM
Blower Size/
Motor HP #
of Speeds
Motor
Speed
From
Factory
Motor
Speed
Constant Torque Motor
CFM wet coil with filter & heaters
External Static Pressure-Inches W.C.
0.10 0.20 0.30 0.40 0.50 0.60 0.70
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
827 804 779 740 708 659 608
1020 1035 1068 1095 1119 1138 1147
198 207 206 204 211 205 189
599 578 544 509 474 ——
832 875 905 935 963 ——
95 96 108 102 112 ——
977 930 898 850 801 746 687
1120 1132 1136 1141 1146 1153 1160
294 271 266 257 239 231 214
811 785 759 726 708 ——
982 1008 1026 1050 1081 ——
177 186 182 188 189 ——
1170 1127 1085 1048 1012 973 943
886 921 958 986 1022 1053 1083
267 275 287 290 301 305 315
1053 1003 969 928 897 ——
835 864 903 933 973 ——
212 216 227 232 242 ——
1316 1275 1229 1191 1151 1093 1039
974 1006 1036 1063 1098 1120 1131
365 378 383 390 399 393 377
1208 1172 1125 1087 1049 ——
906 938 968 1002 1030 ——
284 299 306 315 322 ——
1.5
827/474
8 kW max
10X6 1/3 hp
2 speed
dual voltage
5
3
2
2
977/708
10 kW max
10X6 1/3 hp
2 speed
dual voltage
5
2.5
1170/897
10 kW max
10X8 1/2 hp
2 speed
dual voltage
5
5
4
3
2
3
1316/1049
10 kW max
10X8 1/2 hp
2 speed
dual voltage
5
5
4
NOTE:
Constant torque speed changes
All constant torque motors have 5 speed taps. Speed tap 1 is for continuous fan. Speed tap 2 (low static) and speed tap 3 (high static) are for lower tonnage. Speed
tap 4 (low static) and speed tap 5 (high static) are for higher tonnage.
Constant torque air handlers are always shipped from factory at speed tap 5. To change to 1.5-ton or 2.5 ton airflow, move the blue wire to speed tap 2 or 3 on the
constant torque motor.
The low static speed tap 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5” WC. The high static speed tap 3 (lower tonnage) and 5
(higher tonnage) are used for external static exceeding 0.5” WC. Move the blue wire to the appropriate speed tap as required by the application needs.
The airflow for continuous fan (speed tap 1) is always set at 50% of the speed tap 4.
The above airflow table lists the airflow information for air handlers with maximum heater allowed for each model.