EasyManuals Logo
Home>Siemens>Circuit breakers>3VF Series

Siemens 3VF Series User Manual

Siemens 3VF Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Communication System Manual 3WN6 Circuit-Breakers
52 Copyright Siemens AG 1998. All rights reserved. Version 1.0 (05/98)
3.4.3 List of cyclical 3WN6 data traffic on PROFIBUS-DP
RELEASE
N and P H and J/K D and E/F
PLC output data to 3WN6
(cyclic)
OCTET 9
BIT 15
BIT 14
BIT 13
BIT 12
BIT 11
BIT 10
BIT 9
Acknowledge "Tripped"
signals via bus
48)
BIT 8
OCTET 10
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
Circuit-breaker OFF
49)
BIT 1
X X X
Circuit-breaker ON
50)
BIT 0
X X X
OCTETS 11 and 12
"a" release setting current I
r
[A]
40 -
100 % I
n
X X X
48)
Equivalent of "Clear" button on release unit.
49)
Function only available if circuit-breaker is fitted with shunt release F1 or F2.
50)
Function only available if 3WN6 circuit-breaker is fitted with motorized operating mechanism and closing solenoid Y1.