© Siemens plc 1999 | G85139-H1731-U400-D2 17
CS A High Voltage Three Phase Units
Model: MI37/3 MI55/3 MI75/3 MI110/3 MI150/3
Order Number: *
6SE9611-
1DF[y]0-Z=C87
6SE9611-
4DF[y]0-Z=C87
6SE9611-
8DF[y]0-Z=C87
6SE9612-
7DF[y]0-Z=C87
6SE9613-
7DF[y]0-Z=C87
Motor Output
Rating:
0.37kW
0.49hp
0.55kW
0.73hp
0.75kW
1.0hp
1.1kW
1.5hp
1.5kW
2.0hp
Operating Input
Voltage:
3∅ AC 380 – 500 Vrms ± 10% (all units) 3∅ AC 380 – 480 Vrms ± 10% (filtered units only)
Operating Input
Frequency:
47 – 63 Hz
Output
Frequency:
0 – 50Hz
Output Frequency
with Opm2 or
serial link:
0-400Hz
Input Current: 2.2 A rms 2.8 A rms 3.7 A rms 4.9 A rms 5.9 A rms
Mains fuse: 10 A
Mains Lead cross-
section
1mm
2
* [y] = filter option: 1 = Unfiltered, 5 = Class A filter, 6 = Class B filter.
CS B High Voltage Three Phase Units
Model: MI150/3 MI220/3 MI300/3 MI400/3 MI550/3 MI750/3
Order Number: * 6SE9613-
7DD[y]0-
Z=C87
6SE9615-
8DD[y]0-
Z=C87
6SE9617-
3DD[y]0-
Z=C87
6SE9621-
1DD[y]0-
Z=C87
6SE9621-
3DD[y]0-
Z=C87
6SE9621-
7DD[y]0-
Z=C87
Motor Output
Rating:
1.5kW
2.0hp
2.2kW
2.9hp
3.0kW
4.0hp
4.0kW
5.3hp
5.5kW
7.3hp
7.5kW
10.0hp
Operating Input
Voltage:
3∅ AC 380 – 500 Vrms ± 10% (all units) 3∅ AC 380 – 480 Vrms ± 10% (filtered units only)
Operating Input
Frequency:
47 – 63 Hz
Output
Frequency:
0 – 50Hz
Output
Frequency with
Opm2 or serial
link:
0-400Hz
Input Current: 3.5 A rms 4.7 A rms 6.4 A rms 10.0 A rms 12.2 A rms 16.0 A rms
Mains fuse: 10 A 16 A 20 A
Mains Lead
cross-section
1mm
2
1.5mm
2
2.5mm
2
* [y] = filter option: 1 = Unfiltered, 5 = Class A filter, 6 = Class B filter.
PARAMETER SUMMARY LIST
This list is applicable for operation using Opm2 – Clear Text Display (optional).
● = Parameter can be changed during operation.
✩✩✩ = Value depends on the rating of the motor.