Certification
6.2EMC and Environmental Type Tests
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RS910 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
Test Description Test Levels Severity
Levels
Enclosure
Contact
± 8 kV 4IEC
61000-4-2
ESD
Enclosure Air ± 15 kV 4
IEC
61000-4-3
Radiated RFI Enclosure
Ports
20 V/m
Signal Ports ± 4 kV @ 2.5 kHz x
DC Power
Ports
± 4 kV 4
AC Power
Ports
± 4 kV 4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV 4
Signal Ports ± 4 kV Line-to-Ground
± 2 kV
4
DC Power
Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal Ports 10 V 3
DC Power
Ports
10 V 3
AC Power
Ports
10 V 3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V 3
IEC
61000-4-8
Magnetic Field Enclosure
Ports
40 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-11
Voltage Dips and Interrupts AC Power
Ports
100% for 5 Periods
100% for 50 Periods
IEC
61000-4-12
Damped Oscillatory Signal Ports 2.5 kV Common
Mode @ 1 MHz
3
RUGGEDCOM RS910
Installation Manual, 04/2021, C79000-G8976-1029-12
39