Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity
Levels
1 kV Differential
Mode @ 1 MHz
DC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
AC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
Signal Ports 30 V Continuous
300 V for 1 s
4IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply DC Power
Ports
10% 3
IEC
61000-4-29
Voltage Dips and Interrupts DC Power
Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports 2 kV (Failsafe Relay Output)
DC Power
Ports
1.5 kV
Dielectric Strength
AC Power
Ports
2 kV
Signal Ports 5 kV (Failsafe Relay Output)
DC Power
Ports
5 kV
IEC 60255-5
HV Impulse
AC Power
Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS910 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary
communication loss, while Class 2 requires error-free and interrupted
communications.
Description Test Levels
Enclosure Contact ± 8 kVESD
Enclosure Air ± 15 kV
Radiated RFI Enclosure Ports 35 V/m
Signal Ports ± 4 kV @ 2.5 kHzFast Transient
DC Power Ports ± 4 kV
40
RUGGEDCOM RS910
Installation Manual, 04/2021, C79000-G8976-1029-12