6.2EMC and Environmental Type Tests
Description Test Levels
AC Power Ports ± 4 kV
Earth Ground Ports ± 4 kV
Signal Ports 2.5 kV Common Mode @ 1 MHz
DC Power Ports 2.5 kV Common and
Differential Mode @ 1 MHz
Oscillatory
AC Power Ports 2.5 kV Common and
Differential Mode @ 1 MHz
Signal Ports 5 kV (Failsafe Relay)
DC Power Ports 5 kV
HV Impulse
AC Power Ports 5 kV
Signal Ports 2 kV (Failsafe Relay)
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40
°F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185
°F), 16 Hours
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Db 95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
IEC 60255-21-1 Vibration 2 g @ 10 to 150 Hz Class 2
IEC 60255-21-2 Shock 30 g @ 11 ms Class 2
RUGGEDCOM RS910
Installation Manual, 04/2021, C79000-G8976-1029-12
41

Other manuals for Siemens RUGGEDCOM RS910

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RS910 and is the answer not in the manual?

Siemens RUGGEDCOM RS910 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RS910
CategorySwitch
LanguageEnglish

Related product manuals