RUGGEDCOM RSG2100
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests 45
Description Test Levels
±8 kV
±15 kV
Radiated RFI Enclosure Ports 35 V/m
Signal Ports 4 kV @ 2.5 kHz
DC Power Ports 4 kV
AC Power Ports 4 kV
Fast Transient
Earth Ground Ports 4 kV
Signal Ports 2.5 kV Common Mode @ 1 MHz
DC Power Ports 2.5 kV Common
1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports 2.5 kV Common
1 kV differential mode @ 1 MHz
Signal Ports 5 kV (Fail-Safe Relay Output)
DC Power Ports 5 kV
HV Impulse
AC Power Ports 5 kV
Signal Ports 2 kV
DC Power Ports 2 kV
Dielectric Strength
AC Power Ports 2 kV
Damped Oscillatory
Magnetic Field
Enclosure Ports 100 A/m
Environmental Type Tests
Test Description Test Levels Severity Level
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC
60068-2-30
Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC
60068-21-1
Vibration 2g @ 10-150 Hz
IEC
60068-21-2
Shock 30 g @ 11 ms
IEC
60068-2-78
Humidity (Damp
Heat, Steady State)
Test Cab 10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC
60068-2-14
Change of Temperature Test Nb 5 Cycles, -40 to 85°
C (40 to 185° F)
IEC
60255-21-2
Bump 10 g @ 16 ms Class 1
IEC
60255-21-3
Seismic Method A, Class 2 Class 1

Other manuals for Siemens RUGGEDCOM RSG2200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RSG2200 and is the answer not in the manual?

Siemens RUGGEDCOM RSG2200 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RSG2200
CategorySwitch
LanguageEnglish

Related product manuals