Configuring the HMI device
5.2 Configuring KP300 Basic
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
85
5.2.6 Changing the network configuration
NOTICE
Communication errors caused by IP address conflicts
Communication errors can occur if several devices in a network share the same IP
address.
Assign each HMI device an IP address that is unique within the network.
Procedure
Proceed as follows:
1. Switch to "Info/Settings > Logon/Settings > Transfer/Network > IP Address/Station Name"
menu on the HMI device.
2. To enter a name for the HMI device, enter a name under "Station Name".
Rules for names:
Not more than 240 characters
Characters "a" to "z", numbers "0" to "9"; allow special characters: "-" and "."
Invalid syntax: "n.n.n.n" (n=0 to 999) and "port-yxz" (x, y, z =0 to 9)
3. Select either automatic address assignment via DHCP or manual address assignment:
To acquired the IP address from a DHCP server, set the value under "IP address
static or via DHCP" to "IP via DHCP"
To set a fixed IP address, set the value under "IP address static or via DHCP" to
"static IP".
The entries "IP Address", "Subnet Mask" and "Def. Gateway are also displayed in the
"IP Address/Station Name" menu.
4. If you have assigned a static IP address, enter valid values under "IP Address", "Subnet
Mask" and, if required, under "Def. Gateway".
5. Switch to "Info/Settings > Logon/Settings > Transfer/Network > Network Mode" menu on
the HMI device.
6. If necessary, set the value under "LLDP Protocol" to "Enable".
7. Configure the settings for connection type and transmission rate:
To assign the connection type and transmission rate automatically, set the value
under "Auto Negotiation" to "Enable"".
To assign the connection type and transmission rate manually, set the value under
"Auto Negotiation" to "Disable"".
The entries "Speed" and "Communication Link" are also displayed in the "Network
Mode" menu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI KTP1000 Basic color DP and is the answer not in the manual?

Siemens SIMATIC HMI KTP1000 Basic color DP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI KTP1000 Basic color DP
CategoryControl Panel
LanguageEnglish

Related product manuals