Technical specifications
Installation options
● Wall mounting
● Installation on a DIN rail
● Mounting on an S7-300 standard rail
● Mounting on an S7-1500 standard rail
Mean time between failure (MTBF)
MTBF (EN/IEC 61709; 40 °C) > 48 years
1)
Note the wiring rules (Page 51).
7.6 Technical specifications of the SCALANCE XC224
The following technical specifications apply to the SCALANCE XC224.
Technical specifications
Attachment to Industrial Ethernet
Electrical connectors Quantity 24
Connector RJ-45 jack
Properties Half/full duplex, MDI‑X pinning
Transmission speed 10 / 100 Mbps
Diagnostics interface
Serial interface
Quantity 1
Connector RJ-11 jack
Electrical data
Power supply
1)
Rated voltage 12 to 24 VDC
Voltage range (incl. tolerance) 9.6 to 31.2 VDC Safe Extra Low Voltage
(SELV)
Design Terminal block, 4 terminals
Property Implemented redundantly
Current consumption 12 VDC 750 mA
24 VDC 375 mA
Effective power loss 9 W
Overvoltage category CAT II
Fusing 2.5 A / 125 V
Signaling contact
1)
Quantity 1
Design Terminal block, 2 terminals
Permitted voltage range 24 VDC
Load capability max. 100 mA
Permitted ambient conditions
Ambient temperature During operation up to 2000 m -40 °C to +70 °C
During storage -40 ℃ to +85 ℃
During transportation -40 ℃ to +85 ℃
Relative humidity During operation at 25 ℃ ≤ 95 % no condensation
Technical specifications
7.6 Technical specifications of the SCALANCE XC224
SCALANCE XC-200