Commissioning
7.3 Switching on
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 06/2020, A5E44455710A
95
7.3.1 Test run
After installation or inspection, carry out a test run:
1. Start up the machine without a load. To do this, close the circuit breaker and do not
switch off prematurely. Check whether it is running smoothly.
Switching the machine off again while it is starting up and still running at slow speed
should be kept to a bare minimum, for example for checking the direction of rotation or for
checking in general.
Allow the machine to run down before switching it on again.
2. If the machine is running smoothly and evenly, switch on the cooling equipment. Continue
to observe the machine for a while in no-load operation.
3. If it runs perfectly, connect a load.
NOTICE
Thermal overload of motors connected directly to the line supply
In addition to the load torque, the ramp-up (accelerating) time is essentially influenced
by the moment of inertia to be accelerated. While ramping up when connected to the
line supply, the inrush (starting) current is a multiple of the rated current. This can result
in thermal overload. This can damage the motor.
As a consequence, when ramping up, observe the following:
Monitor the ramp-up time and number of consecutive starts.
Comply with the limit values and/or ramp-up conditions specified in the catalog or the
order documentation.
4. During the test run, check and document the following:
Check whether it is running smoothly.
Document the voltage, current and power values. As far as possible, document the
corresponding values of the driven machine.
If this is possible using the available measuring equipment, check the bearing and
stator winding temperatures until they have reached steady-state values.
Check the machine for noise or vibrations on the bearings or bearing shields as it
runs.

Table of Contents

Other manuals for Siemens SIMOTICS XP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTICS XP Series and is the answer not in the manual?

Siemens SIMOTICS XP Series Specifications

General IconGeneral
BrandSiemens
ModelSIMOTICS XP Series
CategoryEngine
LanguageEnglish

Related product manuals