Date and Time Synchronization
Date format DD.MM.YYYY (Europe)
MM/DD/YYYY (USA)
YYYY-MM-DD (China)
Time source 1, time source 2 None
IRIG-B 002(003)
IRIG-B 006(007)
IRIG-B 005(004) with extension according to
IEEE C37.118-2005
DCF77
PI (protection interface)
34
SNTP
IEC 60870-5-103
DNP3
IEEE 1588
T104
Time zone 1, time zone 2 Local
UTC
Failure indication after 0 s to 3600 s
Time zone and daylight saving time Manually setting the time zones
Time zone offset with respect to GMT -720 min to 840 min
Switching over to daylight saving time Active
Inactive
Beginning of daylight saving time Input: day and time
End of daylight saving time Input: day and time
Offset daylight saving time 0 min to 120 min [steps of 15]
11.3
34
If provided
Technical Data
11.3 Date and Time Synchronization
1116 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018