4 - INSTALLATION
4.21.12 - 1 heating circuit with heat pump integration, DHW, DHW from Pdc, DHW return, solar, 2 tanks ( 1 solar and 1
boiler) and solar transfer function
Figure 4-35 - Hydraulic connection
Settings:
Conguration > System >
Number of Modules 1
Module 1 Heating
Outdoor sensor Yes
DHW Yes
DHW return sensor Yes
DHW Mode Sensor
Unit of measure °C
Number of Zones 1
Antilegionella Yes
Shue type pump Antilegionella
Solar Yes
Solar Atistagnation Yes
Solar Antifrost Yes
Modbus enable No
Heat pump Yes
Conguration > Zones > 3 way valve > 3 way valve 1> Zone type Mix
NOTE: The mixing pump (53) must be set as Anti-legionella.
NOTE: The mixing pump also acts as solar transfer by means of relay R1 and as transfer Pdc by means of relay R2.
NOTE: DHW through the Pdc must be managed independently by the same and not through Tutorbit.