TUTORBIT
COSMOGAS
6 - USE
6.10 - Heating circuits time setting
For the heating circuits time setting, open the Parameters-
>Zones->Programme-> menu
Reset=Yes to reset the time programme set;
Copy=Yes to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If there is no room sensor, the selectable time bands are:
Comfort (on) or O.
If the QMX3 room sensor is present, the selectable time bands
are: Comfort, Precomfort, Reduced, Protection whose
corresponding room temperatures are set to Parameters->
Room unit data n->
If the time slots are di󰀨erent for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the rst day,
you can copy the others, as explained above.
Once the time programme is completed, simply activate it by
setting Parameters->Zone n->Action = Automatic.
6.11 - Cooling circuits time setting
At the rst access of the menu Parameters->Zones->Cool
Timer program anomalous default times will result. In order to
restore consistent values, select Reset = Yes. Then proceed to
ll in the weekly program in the same way as in Section 6.10.
If there is no room sensor, the selectable time bands are:
Comfort (on) or O.
If the QMX3 room sensor is present, the selectable time bands
are: Comfort, Precomfort, Reduced, Protection whose
corresponding room temperatures are set to Parameters->
Room unit data n->.
6.7 - Cooling adjustmen
To deactivate or set the cooling to zones “n” (intended as “n” of
any of the 5 zones) automatically (operation according to the
time bands) or manually (operation at constant temperature)
set Parameters-> Zones -> Zone n -> Action = O or
Automatic or Manual.
If a QMX3 room sensor is present, this Action parameter is not
present and the O or Automatic action must be performed
directly on the room sensor.
When the Action parameter is set in Manual, the supply
temperature to Zone “n” is performed on Parameters-> Zones
-> Cool Supply Setp.
o adjust the compensation reduction in Zone “n”, edit the
Parameters->Zones->Cool Night setback.
Select the required outdoor reset for Zone “n” with the
Parameters->Zones->Cooling Outdoor reset control, then
set the curve parameters as shown in Section 4.11.
Set the time programme for heating Zone “n” with the
Parameters->Zones->Cool Timer Program control, then
set the parameters as shown in Section 6.10.
6.8 - DHW time program
TutorBit is able to set a programme on 3 daily time slots. Open
the Parameters->DHW->Time Programme-> menu
The menu displays the following parameters, in order:
Reset=Yes. to reset the time programme;
Copy=Yes to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If the time slots are di󰀨erent for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the rst day,
you can use the “Copy” command to copy them to the other
days, as explained above.
Once the time programme is completed, simply activate it
by setting Parameters->DHW->DHW action = Automatic.
6.9 - Timer DHW return
Set the timer DHW return by opening the menu Parameters-
>DHW->Timer DHW return->.
The menu displays the following parameters, in order:
Reset=Yes to reset the time programme;
Copy=Yes o copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If the time slots are di󰀨erent for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the rst day,
you can copy the others, as explained above.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TUTORbit POL687 and is the answer not in the manual?

Siemens TUTORbit POL687 Specifications

General IconGeneral
BrandSiemens
ModelTUTORbit POL687
CategoryController
LanguageEnglish

Related product manuals