Specific Guidelines for Wiring a Waterflow Switch to a Class A Zone Module
Circuit is supervised. Supervisory power is 7.3 mA @ 24 VDC.
Rating:
- 20.4 to 32.0 VDC
- 60 mA @ 24 VDC
Connect N/O waterflow contact as shown in the figure. Connect to any zone on
the module.
Figure 19: Class A Monitor
Zone – Waterflow Switch Wiring
Class B Monitor Zone Wiring
Class B Wiring
This section shows typical wiring for a Class B monitor or security device circuit. Fire and security devices connect in the same manner to the following
monitor zone modules.
4100-5001 8 Zone Class B – Connects Fire Initiating Devices Only
4100-5004 8 Zone Class B – Connects either Fire Initiating Devices or Security Devices
4100-5005 8 Zone Class B – Connects either Fire Initiating Devices or Security Devices
4010-9920 8 Zone Class B – Connects Fire Initiating Devices Only
For information on wiring a waterflow switch to a class B monitor zone module, refer to the next section "Class B Waterflow Switch Wiring."
page 20 579-205 Rev. H
4010ES and 4100 4120-Series Class A/Class B Zone Modules Installation Instructions