Specific Guidelines for Wiring a Waterflow Switch to a Class B Zone
Module
If a zone is not used, connect a 3.3 K, 1 W resistor (378-017) across
zone terminals.
EOL Harnesses (not EOL resistors) are required at devices and at
the ends of zone loops.
Connect tamper switch contacts to the appropriate zone. The
zone shown in the figure is an example. Tamper operation is
selected via the Programmer.
Connect NO waterflow and tamper contacts to any zone as shown
in the figure.
Waterflow and Tamper Switch Power Rating:
- 7.2 mA @ 24 VDC
- 60.0 mA @ (Shorted)
Figure 21: Class B Monitor Zone – N.O. Waterflow and
Tamper Switch Wiring (4081-9002 EOL resistor harness)
page 22 579-205 Rev. H
4010ES and 4100 4120-Series Class A/Class B Zone Modules Installation Instructions