7.2 Motor 1 parameter group of F01 group
0: ordinary asynchronous
motor
1: variable-frequency
asynchronous motor
2: permanent magnet
synchronous motor
The A90 series inverter supports asynchronous and synchronous motors. Please set this
parameter correctly according to the actual situation.
Rated power of
electric motor
Depending on the
motor type
Depending on the
motor type
0.01 ~ 600.00 (rated power
of motor: ≤ 75 kW)
0.1 ~ 6000.0 (rated power of
motor: > 75 kW)
Depending on the
motor type
Depending on the
motor type
Depending on the
motor type
Depending on the
motor type
Rated power
factor of motor
Depending on the
motor type
Depending on the
motor type
The above function codes are the nameplate parameters of the asynchronous motor.
When the motor is connected to the inverter for the first time, regardless of VF control or
vector control, the above parameters must be correctly set according to the motor nameplate
before operation.
When the rated power (F01.01) of the motor is changed, the values of F01.03 to
F01.08 of the inverter will change automatically. Pay attention to this during operation.