Safety Instructions
HEC002-A/HEC006-A 2-5
2.3.1 Interlock list
Table2-3 Safety interlock list (Part 1)
No.
Description
Part
Quantity
Location
Cause
1
Overheat in
Heat
Exchanger
Thermostat
1
Heat
Exchanger
Detects abnormal heat in heat
exchanger.
2
Switching
power supply
failure
Thermostat
2
Power supply
Detects abnormal current, voltage or
heat.
3
Overheat in
Heat Sink
Thermostat
1
Heat sink
Detects overheat in Heat Sink.
4
Low circulating
fluid level
Level sensor
1
Reservoir
Detects lowering of circulating fluid level
in reservoir.
5
Detection of
breakage of
temp. sensor
Controller
internal circuit
-
Detects breakage and short circuit of
temp. sensor and cables.
6
Excessive
temp. increase
Controller
internal circuit
-
Detects temp. input value not less than
70 C.
7
Excessive
temp.
decrease
Controller
internal circuit
-
Detects temp. input value not more than
0 C.
8
Abnormal
output
(Overload)
Controller
internal circuit
-
Works when temp. change is smaller
than over load detection temp.(selected
between 0.1 to 9.9 C) even if 100%
output continues during overload
detection time (selected between 0 to
99min.) When 0 is set, the alarm doesn’t
arise.
9
Low flow rate
(Option)
Flow sensor
-
Detects lowering of flow rate at
0.7±0.3L/min or less.
Table2-4 Safety interlock list (Part 2)
No.
Description
Condition of unit
Indication
How to reset
1
Overheat in Heat
Exchanger
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR14)
Restart power
supply
2
Switching power
supply failure
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR11)
Restart power
supply
3
Overheat in Heat
Sink
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR14)
Restart power
supply
4
Low circulating fluid
level
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR20)
Restart power
supply

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HEC002-A5 and is the answer not in the manual?

SMC Networks HEC002-A5 Specifications

General IconGeneral
BrandSMC Networks
ModelHEC002-A5
CategoryController
LanguageEnglish

Related product manuals