EasyManuals Logo
Home>SMC Networks>Controller>HEC002-A5

SMC Networks HEC002-A5 User Manual

SMC Networks HEC002-A5
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Safety Instructions
HEC002-A/HEC006-A
2-6
5
Detection of
breakage of temp.
sensor
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR17)
Restart power
supply
6
Excessive temp.
increase
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR12)
Restart power
supply
7
Excessive temp.
decrease
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display
(ERR13)
Restart power
supply
8
Abnormal output
(Overload)
The unit continues to
operate.
Error indication on display
(ERR15)
Restart power
supply
9
Low flow rate
(Option)
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display
(ERR16)
Restart power
supply
2.4 Disposing of product
Contact an industrial waste disposal company for disposal of the product.
To minimize the risk, drain the fluid from the product when it is scrapped. If the fluid is left inside, an
accident and damage can result during transportation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HEC002-A5 and is the answer not in the manual?

SMC Networks HEC002-A5 Specifications

General IconGeneral
BrandSMC Networks
ModelHEC002-A5
CategoryController
LanguageEnglish

Related product manuals