Operation
HEC002-A/HEC006-A 8-7
5. Offset Value
Setting range : -9.99 to 9.99 C
Min. increment : 0.01 C
Indicated content : Offset value(Ex. : -0.15 C)
Function : It allows the change of the difference between
the controller reference value and set value by
offset.
For example, if -0.15 C is set here, the actual reference temperature for control is
lower than the indicated SV by 0.15 C.
6. Allowable Upper Temp. Range
Setting range : 0.1 to 10.0 C
Min. increment : 0.1 C
Indicated content : Temp. from target to upper limit
(Ex.: 1.5 C)
Function : Sets upper limit of temp. where the warning arises. The difference between target
temp. and upper limit temp. should be input. Therefore, if the target temp. is 23.0
C and 1.5 C is set in this item, the warning [WRN] arises when temp. exceeds
24.5 C.
7. Allowable Lower Temp. Range
Setting range : 0.1 to 10.0 C
Min. increment : 0.1 C
Indicated content : Temp. from target to lower limit
(Ex. : 1.5 C)
Function : Sets lower limit of temp. where the warning arises. The difference between target
temp. and lower limit temp. should be input. Therefore, if the target temp. is 23.0
C and 1.5 C is set in this item, the warning [WRN] arises when temp. lowers
21.5 C.
8. High Temp. Cutoff
Setting range : 11.0 to 70.0 C
Min. increment : 0.1 C
Indicated content : High temp. cutoff by internal temp.
sensor (Ex. : 70.0 C).
Function : Sets upper limit of temp. at which the internal temp. sensor detects and judges the
unit should be shut off. When the temp. set in this item is reached, the alarm
[ERR12] arises.
9. Low Temp. Cutoff
Setting range : 0.0 to 59.0 C
Min. increment : 0.1 C
Indicated content : Low temp. cutoff by internal temp.
sensor (Ex. : 0.0 C)
Function : Sets lower limit of temp. at which the internal temp. sensor detects and judges the
unit should be shut off. When the temp. set in this item is reached, the alarm
[ERR13] arises.
O f f s e t V a l u e
M O D E < - 0 . 1 5 C
A l l o w a b l e U p p e r
T e m p . R a n g e
M O D E < 1 . 5 C
A l l o w a b l e L o w e r
T e m p . R a n g e
M O D E < 1 . 5 C
H i g h T e m p .
C u t o f f
M O D E < 7 0 . 0 C
L o w T e m p . C u t o f f
M O D E < 0 . 0 C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HEC002-A5 and is the answer not in the manual?

SMC Networks HEC002-A5 Specifications

General IconGeneral
BrandSMC Networks
ModelHEC002-A5
CategoryController
LanguageEnglish

Related product manuals