Technical Specifications - Three Phase Inverters
for Europe &APAC for 220/380V, and 230/400V
Grids
SE25K, SE27.6K, SE30K, SE33.3K
SE25K SE27.6K SE30K SE33.3K Unit
Applicable to inverters with part
numbers
SEXXK-XXX0IXXXX
Output
Rated AC Active Output Power
25000
(1)
27600 29990 33300 W
Maximum AC apparent Output Power 25000
(1)
27600 29990 33300 VA
AC Output Line Connections 3W + PE, 4W + PE
AC Output Voltage - Line to Line /
Line to Neutral (Nominal)
380 / 220 ; 400 / 230 Vac
AC Output Voltage - Line to line / Line
to Neutral
304 - 437 / 176 - 253 ; 320 - 460 /184 -
264.5
Vac
AC Frequency 50/60 ± 5% Hz
Maximum Continuous Output Current
(per phase)
36.25 40 43.5 48.25 A
Maximum continuous overcurrent
protection
36.25 40 43.5 48.25 A
Residual current detector / Residual
Current step detector
100 / 30 mA
Grid Supported – three phase WYE: TN-C, TN-S, TN-C-S, TT, IT; Delta: IT
Inrush current AC (Peak/Duration) 3.6 / 20
Aac
(rms)
/ ms
Maximum output fault current 54.45 58.55 66.4 47.1 A
Power Factor Range +/- 0.8 to 1
Maximum residual output current 100 mA
Total Harmonic Distortion ≤ 3%
Protective class Class I
Utility Monitoring, Islanding
Protection, Configurable Power
Factor, Country Configurable
Thresholds
Yes
(1)
24.99kVA in the UK
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX
71 Technical Specifications - Three Phase Inverters for Europe &APAC for
220/380V, and 230/400V Grids