Three Phase Inverter for the 277/480V Grid - SE33.3K,
SE40K
SE33.3K SE40K Unit
Applicable to inverters with
part numbers
SEXXK-XXX8IXXXX
Output
Rated AC Active Output Power 33300 40000 W
Maximum Apparent AC Power
Output
33300 40000 VA
AC Output Line Connections 3W + PE, 4W + PE
AC Output Voltage - Line to
Line / Line to Neutral
(Nominal)
480 / 277 Vac
AC Output Voltage - Line to
Neutral Range
244-305 Vac
AC Frequency 50/60 ± 5% Hz
Maximum Continuous Output
Current (per Phase)
40 48.25 A
Maximum continuous
overcurrent protection
40 48.25 A
Residual current detector /
Residual Current step detector
100 / 30 mA
Grid supported – three phase
WYE: TN-C, TN-S, TN-C-S, TT; IT
Delta: IT
Inrush current AC
(Peak/Duration)
5.2 / 20 Aac(rms) / ms
Maximum output fault current 58.55 47.1 A
Power Factor Range +/-0.8 to 1
Maximum residual output
current
100 mA
Total Harmonic Distortion 3%
Protective class Class I
Utility Monitoring, Islanding
Protection, Configurable
Power Factor, Country
Configurable Thresholds
Yes
Overvoltage category III
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX
75 Three Phase Inverter for the 277/480V Grid - SE33.3K, SE40K