34
|
Accessories
5.3.2 Duct water heater
A duct water heating battery is supposed to be installed in supply air duct.
WH water heating battery
FPT frost protection sensor
SAT supply air temperature sensor
S actuator for valve
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
Component/product Article number:
RVAZ4 24A Actuator 0-10V (S) 9862
Duct sensor -30-70C (SAT) 211524
Surface sensor -30-150C (FPT) 211523
Transformer 24V 202692
VSR 300:
VBC 160-2 Water heating battery— 5458
VBC 160-3 Water heating battery 9840
ZTV 15-0,4 2-way valve 9829
ZTV 15-0,6 2-way valve 6571
ZTR 15-0,4 valve 3-way 9670
ZTR 15-0,6 valve 3-way 6573
VSR 500:
VBC 200-2 Water heating battery— 5459
VBC 200-3 Water heating battery 9841
ZTV 15-0,6 2-way valve 6571
ZTV 15-1,0 2-way valve 9823
ZTR 15-0,6 valve 3-way 6573
ZTR 15-1,0 valve 3-way 9672
Fig. 9 Water heater connections
Installation and connection
1. Install water heater in the duct. Connect pipes, 2/3–
way valve and actuator.
Important
Do NOT use 24V DC power output from the
connection board for valve actuator.
2. Connect actuator (S) to any free analog output.
3. The frost protection sensor (FPT) should be strapped on a surface on the return water pipe. Connect FPT sensor to
any free analog input.
4. An internal supply air temperature sensor (SAT, default connection AI2 on the main circuit board) must be replaced
by a duct temperature sensor which can be acquired as an accessory. A duct temperature sensor must be installed in
the duct after water heater. Connect the duct temperature sensor to analog input 2 (AI2) replacing the internal supply
air temperature sensor.
Note:
A duct temperature sensor can be connected to analog inputs 6–7 on the connection board for better
access and then configured as a supply air temperature sensor. However the internal supply air
temperature sensor must be disabled in the control panel first.
Configuration
1. Go to Service menu
2. Enter password (default 1111)
3. Activate the actuator. Go to Components menu, select Heater menu and select type as Water. Choose actuator
voltage type. Do advanced settings if necessary.
| v1

Other manuals for SystemAir SAVE VSR 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir SAVE VSR 300 and is the answer not in the manual?

SystemAir SAVE VSR 300 Specifications

General IconGeneral
BrandSystemAir
ModelSAVE VSR 300
CategoryFan
LanguageEnglish

Related product manuals