20
TECHNICAL DATA
— Relays
Quantity 7—11—15—31
Type Changeover (SPDT, type C)
Make (SPST-NO, type A)
Rated current 8 A
Short duration current (0,5 s) 30 A
Rated voltage/max switching voltage 250 V~/400 V~
Make 1000 W/VA
Minimum switching load 300 mW (5 V/ 5 mA)
Life
• Mechanical 10
6
• Electrical 10
5
Breaking capacity:
• Direct current (L/R = 40 ms) 50 W
• Alternating current (l = 0,4) 1250 VA
Minimum pulse width 0....500 ms (step 5 ms)
— Block output (Logic selectivity)
Quantity 1
Type optocoupler
3.4 MMI (MAN MACHINE INTERFACE)
Display 60x85 graphic LCD
LEDs
Total Number 21
• ON/fail (Green) 1
• Remote 1
• Local 1
• Start (Yellow) 1
• Trip (Red) 1
• Programmables (Red) 16
Touchscreen Keyboard 10 keys
Keyboard 10 keys
3.5 COMMUNICATION INTERFACES
— Local port
Ethernet 100 BaseT 100 Mbps
• Connector RJ45
— Network ports
RS485 1200...57600 bps
• Connection screw terminals
Ethernet 100BaseT
[1]
100 Mbps
• Connection Optical fiber 1300 nm, ST
100 Base TX, RJ45
— Protocol
ModBus RTU/IEC60870-5-103/DNP3,
ZCP/IP, IEC61850 Level A
Note [1] Two redundant port selectable with TX + TX or FX + FX connections. The secondary port
is activated in the event of failure of the primary port or by means of hw-sw switching command.
3.6 RATED VALUES AND GENERAL SETTINGS
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021