18
1 SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Smart Cassette
<Single type>
Model
Indoor unit RAV-GM 561UT* 801UT*
Outdoor unit RAV-GP 561ATW* 801ATW*
Cooling capacity (kW) 5.0 7.1
Heating capacity (kW) 5.6 8.0
Power supply 220 - 240 V ~, 50 Hz
(Power supply from outdoor unit)
Electrical
characteristics
Cooling Running current (A) 5.72-5.24 6.70-6.14
Power consumption (kW) 1.20 1.37
Power factor (%) 94 93
EER 4.17 5.18
SEER 8.07 9.40
Energy efficiency class (Lot10) A++ A+++
Heating Running current (A) 6.22-5.70 7.01-6.43
Power consumption (kW) 1.29 1.45
Power factor (%) 93 94
COP 4.34 5.52
SCOP 5.01 5.51
Energy efficiency class (Lot10) A++ A+++
Maximum current (A) 13.1 20.3
Indoor unit
Fan unit
Fan Turbo fan Turbo fan
Standard air flow (H/M+/M/L+/L) (m³/min) 17.5/16.5/15.0/13.5/12.5 32.0/23.2/21.5/19.0/13.5
Motor (W) 60 130
Sound pressure level (H/M+/M/L+/L) (dB(A)) 32/31/29/28/26 42/37/35/32/27
Sound power level (H/M+/M/L+/L) (dB(A)) 48/47/45/44/43 56/50/49/46/43
Outdoor unit
Length of refrigerant
pipe
Max. total length (m) 50 50
Min. length (m) 3 3
Height
difference
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Fan unit
Fan Propeller fan Propeller fan
Standard air flow high (m³/min) 37.5 53
Motor (W) 43 60
Connecting pipe
Outdoor unit-
Pipe branch
Gas side (mm) 12.7 15.9
Liquid side (mm) 6.4 9.5
Pipe branch-
indoor unit
Gas side (mm) 12.7 15.9
Liquid side (mm) 6.4 9.5
Sound pressure level Cooling/Heating (dB(A)) 46/48 46/48
Sound power level Cooling/Heating (dB(A)) 63/65 63/66