21
1-1-4. Compact 4-Way Cassette
<Twin type>
Model
Indoor unit RAV-RM
401MUT*
Indoor unit2 RAV-RM
401MUT*
Outdoor unit RAV-GP
801ATW*
Cooling capacity (kW)
7.1
Heating capacity (kW)
8.0
Power supply
220 - 240 V ~, 50 Hz
(Power supply from outdoor unit)
Electrical
characteristics
Cooling Running current (A)
8.46-7.75
Power consumption (kW)
1.73
Power factor (%)
93
EER
4.10
SEER
7.80
Energy efficiency class (Lot10)
A++
Heating Running current (A)
8.80-8.07
Power consumption (kW)
1.82
Power factor (%)
94
COP
4.40
SCOP
4.86
Energy efficiency class (Lot10)
A++
Maximum current (A)
20.8
Indoor unit
Fan unit
Fan
Turbo fan
Standard air flow (H/M+/M/L+/L) (m³/min)
11.0/10.2/9.2/8.0/7.8
Motor (W)
60
Sound pressure level (H/M+/M/L+/L) (dB(A))
41/38/36/33/32
Sound power level (H/M+/M/L+/L) (dB(A))
56/53/51/48/47
Outdoor unit
Length of refrigerant
pipe
Max. total length (m)
50
Min. length (m)
3
Height
difference
Outdoor lower (m)
30
Outdoor high (m)
30
Fan unit
Fan
Propeller fan
Standard air flow high (m³/min)
53
Motor (W)
60
Connecting pipe
Outdoor unit-
Pipe branch
Gas side (mm)
15.9
Liquid side (mm)
9.5
Pipe branch-
indoor unit
Gas side (mm)
12.7
Liquid side (mm)
6.4
Sound pressure level Cooling/Heating (dB(A))
46/48
Sound power level Cooling/Heating (dB(A))
63/66