EasyManuals Logo
Home>Trane>Chiller>CVHE

Trane CVHE Troubleshooting

Trane CVHE
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
CVHE-SB-32A 118
Information on the Printer Option
Th Printer module is essentially a TCI comm 4 board with a daughter board installed to
communicate RS232 to the Printer. The Printer module is a listen only device and its software
revision level will not show up in service tests.
The diagnostic LED in the upper left hand side of the module is only active for the printer module,
and when it is on, this indicates a loss of communications with the Chiller module.
The Green LED labeled RXA should be continuously flashing.
The Red LED labeled TXA should never come on.
The Green LED labeled RXB will blink once every few seconds while the Printer module is
printing, only if X-ON X-OFF handshaking is enabled.
The Red LED labeled TXB will blink constantly while the printer is printing.
The DIP switch settings for the Printer module follow:
1-off
2-off
3-on
Dip switch settings for the Okidata Microline 184 turbo printer follow:

Table of Contents

Other manuals for Trane CVHE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CVHE and is the answer not in the manual?

Trane CVHE Specifications

General IconGeneral
BrandTrane
ModelCVHE
CategoryChiller
LanguageEnglish

Related product manuals