CVHE-SB-32A 32
Temporary Forced Unload Setup
The following will work if you have the need to temporarily unload the unit for a
specific requirement.
1 Set the front panel current limit setpoint at your requirements, (say 40%)
2 Set the current limit setpoint source to external source.
3 Provide a 10 VDC or 20 mA input signal to J7 11,12.
4 Provide a binary switch to enable/disable the input to J7.
5 With the binary switch closed the unit will operate with a 100% current limit.
6 With the binary switch open the unit will operate with a 40% current limit.