CVHE-SB-32A 85
Key:
Note: The transition complete contact closure is expected to be an auxiliary
contact to the “Run Contactor’ (2K2).
Interval Units Actual
A. (Test for transition complete input open) 160 to 240 msec
B. (Just delay time) 20 msec
C. Close 1M (2K1) Contactor and test for no current.)
(Starter integrity test)
500 msec
D. 1 sec
E. (Open1M (2K1) 200 msec
F. (Close Shorting Contactor (2K3) and test for no current,
then wait for Start command) (Starter integrity test)
1.0 sec (Min.)
G. (Close 1M (2K1) sec 2sec
H. (Wait 1.5 sec after phase currents drop to 85%) sec 1.5 sec
J. (Close 2K4 Transition Contactor) msec 100 msec
K. (Open S (Shorting) Contactor msec 260 msec
L. (Close 2M (2K2) Contactor) 140 msec
M. (Wait to look for Transition complete) N. (Filtering time
on Transition complete input)
msec 2.32 to 2.38sec
N. (Filtering time on Transition complete input) msec 160 to 240 sec