CVHE-SB-32A 46
Duplex Module
The Duplex Chiller control is accomplished by the Duplex Control Module (DCM). The DCM is a
Trane Communications Interface (TCI) based module. Its two main tasks are setpoint control and
compressor staging/control
The DCM will actually control two separate UCP2 panels (“Panel A” and “Panel B”). These
panels are for the most part identical and know nothing of each other. All coordination between
panels is handled with the DCM.
Figure 9
Duplex Module
Panel A IPC Input
Panel B IPC input
J1
J3
J2