CVHE-SB-32A 71
113.0 4299 4434 1.892 1.935
114.0 4207 4339 1.866 1.909
115.0 4117 4246 1.841 1.884
116.0 4029 4155 1.816 1.859
117.0 3944 4067 1.792 1.834
118.0 3861 3980 1.767 1.809
119.0 3779 3896 1.743 1.785
120.0 3700 3814 1.719 1.760
Table 18
Bearing Temp., Oil Temp. and Compressor Discharge Temp.
Temp °°F Min Res Max Res Min Vterm Max Vterm
121.0 3623 3734 1.696 1.736
122.0 3547 3655 1.672 1.712
123.0 3474 3579 1.649 1.689
124.0 3402 3505 1.626 1.666
125.0 3332 3433 1.604 1.643
126.0 3264 3362 1.581 1.620
127.0 3197 3293 1.559 1.598
128.0 3132 3226 1.537 1.575
129.0 3069 3160 1.516 1.553
130.0 3006 3096 1.494 1.531
131.0 2946 3033 1.473 1.510
132.0 2886 2971 1.452 1.488
133.0 2828 2912 1.431 1.467
134.0 2772 2853 1.411 1.447
135.0 2716 2796 1.391 1.426
136.0 2662 2740 1.371 1.406
137.0 2610 2685 1.351 1.385
138.0 2558 2632 1.331 1.365
139.0 2508 2580 1.312 1.346
140.0 2458 2529 1.293 1.326
141.0 2410 2479 1.274 1.307
Table 17 (Continued)
Temp °°F Min Res Max Res Min Vterm Max Vterm