When the VFD bypass option is selected, each supply
and relief/return fan is protected by a motor overload
when in VFD bypass mode. On 60-75T units with dual
DDP supply fan motors (with or without VFD bypass
option), each supply fan motor is protected by a motor
overload in both standard operation and VFD bypass
mode. The motor overloads are factory set to the motor
FLA value and should not be adjusted. If the current to
the motor exceeds the overload dial setting value, the
overload relay auxiliary contacts will trip and interrupt
the control signal to the run and bypass contactor coils.
This will remove power from the fan motor and stop
operation.
Table 63. Filter data
Unit Model (AC/EC)
Panel-Type Filters
(a)
Bag-Type Filters
(b)
Cartridge Filters (Pre-
Evap and Final) (box-
type)
(b)
Panel-Type Prefilters
(Pre-Evap and Final)
(c)
Qt-
y
Size of each
Qt-
y.
Size of each
Qty. (Pre-
Evap/Final
Filter)
Size of each
Qty. (Pre-
Evap/Final
Filter)
Size of
each
20 & 25 ton 12 20 X 20 X 2
4 12 X 24 X 19
4/4
12 X 24 X 12
4/4
12 X 24 X 2
3 24 X 24 X 19
3/3
24 X 24 X 12
3/3
24 X 24 X 2
30 ton 16 20 X 20 X 2
2 12 X 24 X 19
2/1
12 X 24 X 12
2/1
12 X 24 X 2
6 24 X 24 X 19
6/6
24 X 24 X 12
6/6
24 X 24 X 2
40 ton 16 20 X 25 X 2
5 12 X 24 X 19
5/5
12 X 24 X 12
5/1
12 X 24 X 2
6 24 X 24 X 19
6/6
24 X 24 X 12
6/6
24 X 24 X 2
50, 55 ton
20 20 X 25 X 2
3 12 X 24 X 19
3/2
12 X 24 X 12
3/2
12 X 24 X 2
9 24 X 24 X 19
9/9
24 X 24 X 12
9/9
24 X 24 X 2
60, 70 & 75 ton
35 16 X 20 X 2
6 12 X 24 X 19
6/6
12 X 24 X 12
6/6
12 X 24 X 2
8 24 X 24 X 19
8/8
24 X 24 X 12
8/8
24 X 24 X 2
90-130 25 24 X 24 X 2
3 12 X 24 X 19
3/5
12 X 24 X 12
3/5
20 X 24 X 2
15 24 X 24 X 19
15/10
24 X 24 X 12
15/10
24 X 24 X 2
(a)
Dimensions shown for “Panel-Type Filters” apply to “Throw away”, “Cleanable Wire Mesh”, and “High Efficiency Throw away” Filters.
(b)
Units ordered with “Bag-Type Filters” or “Cartridge Filters” (box-type) include a bank of “Panel-Type Prefilters”
(c)
The same “Panel-Type Prefilters” are used with “Bag-Type” and “Cartridge (box-type)” filters.
Table 64. “Wet heat” coil fin data
Unit Model(AC/EC) Coil Type
Coil Rows
Total Coil Face
Area (sq. ft.)
Fins per
Foot
Fins per
Foot
20, 25, 30 ton WC Prima Flo (hot water)
2 13.75 80 110
40, 50, 55 ton WC Prima Flo (hot water)
2 19.25 80 110
60, 70, 75 ton WC Prima Flo (hot water)
2 26.25 80 110
40, 50 ton NS (steam)
1
13.75 (1) 5.5 (1)
42 96
90-130 ton
NS (steam)
1
17.5 (2)
52 96
Note: To determine unit heating capacity (i.e. “low heat” or “high heat”), see digit 9 of the model number stamped on the unit nameplate.
SSeerrvviiccee aanndd MMaaiinntteennaannccee

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak 1 and is the answer not in the manual?

Trane IntelliPak 1 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak 1
CategoryAir Conditioner
LanguageEnglish

Related product manuals