116 RTAA-SVX01A-EN
Periodic Maintenance
Manually rotate condenser fans to insure proper clearance on the fan
openings.
Annual Maintenance
Perform all weekly and monthly maintenance procedures.
Check the oil level and refrigerant charge. Refer to “Maintenance Proce-
dures”. Routine changing of oil is not required. See Oil Separator Level
Check in the Maintenance section of this manual.
Have a qualified laboratory perform a compressor oil analysis to deter-
mine system moisture content and acid level. This analysis is a valuable
diagnostic tool.
Contact a qualified service organization to leak test the chiller, to check
operating and safety controls, and to inspect electrical components for
deficiencies.
Inspect all piping components for leakage and damage. Clean out any
inline strainers.
Clean and repaint any areas that show signs of corrosion.
Clean the condenser coils. refer to RTAA-SB-20 and RTAC-SVG01A-EN.
Clean the condenser fans. Check the fan assemblies for proper clearance
in the fan openings and for motor shaft misalignment, abnormal end-play,
vibration and noise.