EasyManuals Logo
Home>Trane>Chiller>RTAA-70

Trane RTAA-70 User Manual

Trane RTAA-70
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #116 background imageLoading...
Page #116 background image
116 RTAA-SVX01A-EN
Periodic Maintenance
Manually rotate condenser fans to insure proper clearance on the fan
openings.
Annual Maintenance
Perform all weekly and monthly maintenance procedures.
Check the oil level and refrigerant charge. Refer to “Maintenance Proce-
dures”. Routine changing of oil is not required. See Oil Separator Level
Check in the Maintenance section of this manual.
Have a qualified laboratory perform a compressor oil analysis to deter-
mine system moisture content and acid level. This analysis is a valuable
diagnostic tool.
Contact a qualified service organization to leak test the chiller, to check
operating and safety controls, and to inspect electrical components for
deficiencies.
Inspect all piping components for leakage and damage. Clean out any
inline strainers.
Clean and repaint any areas that show signs of corrosion.
Clean the condenser coils. refer to RTAA-SB-20 and RTAC-SVG01A-EN.
Clean the condenser fans. Check the fan assemblies for proper clearance
in the fan openings and for motor shaft misalignment, abnormal end-play,
vibration and noise.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane RTAA-70 and is the answer not in the manual?

Trane RTAA-70 Specifications

General IconGeneral
BrandTrane
ModelRTAA-70
CategoryChiller
LanguageEnglish

Related product manuals